Simplex 4004R

Fire Alarm Control Panel

The Simplex 4004R Release Control Panel is a fire alarm control panel specifically designed for automatic fire suppression systems such as deluge, preaction, and gas suppression. This panel provides full control and monitoring of fire suppression devices, featuring flexible monitoring capabilities, additional relays, and an easy-to-use interface. An ideal solution for liquid-based, gas-based, and specialized sprinkler fire protection systems.

Key Features:

  • Specifically designed for suppression release systems
  • Controls and monitors automatic fire suppression systems.
  • Supports deluge, preaction, foam, and gas systems.
  • Dual Releasing Application Circuits (RACs)
    Two Class B RAC circuits with independent control and full monitoring.
  • Four Class B IDCs (Initiating Device Circuits)
    Supports up to 25 detectors per IDC, with the option to convert to Class A.
  • LED Display & Simple Operation Panel
    Direct visual monitoring and quick operation by technicians.
  • Support for Supervision & Fault Monitoring Functions
    Includes detection of open/short circuits and power loss.
  • Model: Simplex 4004R
  • Panel Type: Release Control Panel
  • Number of IDCs (Inputs): 4 Class B IDCs (optional conversion to Class A)
  • Releasing Circuits (RACs): 2 Class B (max. 2.5 A per RAC), convertible to Class A
  • Relay Output:

    1 Alarm Relay (Form C)

    1 Trouble Relay (Form C)

    1 Supervisory Relay (Form C)

    Optional additional relays up to 3 (Form C)

  • Additional Communication: Port for expansion and remote monitoring
  • Operating Voltage: 24 VDC nominal
  • Battery Capacity: Up to 26 Ah (internal), can be expanded with an external cabinet
  • Certification Standards:

    UL Listed

    ULC Listed

    FM & CSFM Approved

    UL Standard 864

    ULC Standard S527-99

  • Gas fire protection systems (clean agents such as FM-200, Novec 1230)
  • Foam and pressurized water extinguishing systems (deluge & preaction)
  • Industrial installations, server rooms, electrical panels, and generator rooms
  • Automatic control for preaction sprinkler system activation
  • Commercial buildings and critical facilities with automatic fire suppression requirements